D-4 CVT Type AVR / Stabilizer (ELA)

D-4 CVT Type AVR / Stabilizer (ELA)

D-4 CVT Type AVR / Stabilizer (ELA)


Product Specifications

Product introduction
Specially for high precision instrument CVT Type Automatic Voltage Regulator is in small size, maintenance –free and service – free. It is highly adaptable to demand environment. Solid and durable resonance AVR has the following 10 advantages and will be the top choice for you in selecting AVR.

 

Related information

Feature

  • Determined CVT Type AVR
       Output wave is sine wave and is not affected by input waveform
 
  • Fortified CVT Type AVR
    No electronic controlled circuit, only made up with 2 independent element. Excellent voltage regulation function and probability of mis-action is zero
 
  • Most durable CVT Type AVR
      Simple structure, excellent durability, extremely long MTBF-40 years overseas, in Taiwan, has been in service since 1973 (20 years warranty for the main body)
 
  • Delicate designed CVT Type AVR
     Output end short circuit or overload, current will be limited automatically and is ready for use when short circuit or overload is excluded (short circuit for 24 hours will not cause any damage)
 
  • Total insulation between input and output
      Best noise filtering function (higher than 60 db). Best resistance to thunder strike, noise, electrostatic and high voltage pulse
 
  • Perfect Protection
     Uninterrupted Power Supply (UPS) characterized, power off 1-2 cycle (3/4 load) has not effect on output
 
  • Wide Range Input Voltage
      Under drastic rise or drop of input voltage (±45%) output voltage will be steady at ±2.5%
 
  • Excellent Response Time
       Response Time is extremely rapid and is within 1.5 cycle
 
  • Viable Application
       Input voltage 110V or 220V Output voltage can have 110V/ 220V at the same time (2KVA and above)
 
  • AVR main body generates no noise
      The main body is ultra-insulated transformer that prevents peak wave, sink wave and high/low frequency and has best interference fending ability (more than 60db)


Application
  • Electronic Test Instrument
  • R&D Instrument
  • Optoelectronic Industry
  • Multimedia Equipment
  • Industrial Computer
  • Audio Equipment

Model & Specification
   Model No. (ELA-) 105 110 120 130 150
    Capacity (KVA) 0.5 1 2 3 5
Voltage A  : 1ψ2W 110V 60Hz
B : 1
ψ2W 220V 60Hz
B-5 : 1
ψ2W 220V 50Hz

(The output is 1ψ3W 110V-0-110V from 2KVA)
      Input Range +15%-20%
   Input Voltage Fluctuates
       Drastically
±45%
Output Accuracy ±1%, while input voltage within +15% ~ -20%
±1.5%, while input voltage and load changed at the same time
±2.5%, while input voltage within ±45% (3/4 Load)
  Output Voltage Fixed Inside without electronics circuit, to avoid mis-adjusting and make output voltage inaccurately
     Response Time 1.5 cycle
       Distortion SHD:3% THD:5%
      Noise Filter 60db
      Efficiency 90%
    Protect Device Short circuit or overload will have current limited automatically (not auto trip and cut off the power design)
     Environment Temperature: -20~50 Humidity: 0%~95% (non-condensing)
 Dimension WxHxD (cm) 21x19x35 27x46x49