F-1 AFC series AC Power Source

F-1 AFC series AC Power Source

F-1 AFC series AC Power Source


Product Specifications

Product introduction
The AFC Series is an economically priced AC power source to provide reliable voltage and frequency simulation for general applications, such as testing for home appliance, electronic, medical equipment, lighting and other fields of production or R&D.
Utilized PWM switching technology, AFC provides high quality pure sine waveform with output level up to 2,000kVA. The AC source is coupled with output voltage range of 5~300V and output frequency of 47~63Hz, 50/60Hz fixed. User can select optional frequency output of 2 or 4 times standard frequency and 400Hz.


Feature

  • Single phase power output from 0.5-150kVA and three phase power output from 6-2000kVA.
  • CE mark with high electromagnetic compatibility performance.
  • High input power factory and high efficiency up to 92%
  • Coupled with 4 LED displays to show measurements of voltage, current, frequency and power at once.
  • Patented power module design with compact size for easier maintenance and high power density.
  • Comprehensive protection includes over voltage, over current, over load, input under voltage and over temperature with corresponding error codes.
  • Emergency stop button to shut down output immediately.
  • Optional RS232 and RS485 interfaces available.

Related information

Application

Type Output Frequency Range Applications
A
(Standard)
47~63Hz Adjustable,
50/60Hz Selectable
Industrial Product Testing, Production Line Power, Chamber
Power, Burn-in Testing
B 45~500Hz Adjustable Laboratory Testing, Electrical Safety Test
C 350~450Hz Adjustable, 400Hz Military Stationary Power, Product Testing
D 47~63Hz Adjustable,
50/60/2F/4F/400Hz selectable
Transformer Testing
E 50/60Hz Selectable Clean Power Source, Harmonics Isolation
Variable Voltage Power, Frequency Conversion


Model & Specification

   AFC Series-Single Phase Unit

Single-phase output models

Model
Output Input Dimensions (WxDxH)
mm / inch

Chassis No.

Weight KG / lbs

Power

Phase
Voltage (Vrms)
Frequency
Current / Phase
THD

Regulation
Frequency Accuracy
Efficiency

Voltage

Frequency
Power factor
Low
(Arms)
High
(Arms)

AFC-500W

500W
Low(V): 0-150VAC
High(V):
0-300VAC




A
(Standard) 47~63Hz,
50/60Hz
B    45~500Hz

C      350~450Hz,
400Hz
D    47~63Hz,
50/60/2F/
4F/400Hz
E    50/60Hz

4.2

2.1

0.50%

£0.5%











£0.01%
110/ 220 V
± 15% (1Ø2W +G)











³0.8
430x520x200/
17x20.5x7.9


44/97
AFC-11003 3 KVA







Low(V):
5-150 VAC
High(V): 10-
300VAC (L-N)
25 12.5

120V
or 220 V
± 15% (1Ø2W +G)
430x520x720 /
17x20.5x28.4

73/161
AFC-11005 5KVA 41.7 20.8 89/196.3
AFC-11010 10KVA 83.3 41.7 600x850x945/ 210/461
23.7x33.5x37.3
AFC-11015 15KVA


1Ø2W
+G
125.0 62.5
£2% * (opt.
£1%)





± 1% *


³90%



50 or 60 ±3
Hz
600x850x1340 /
23.7x33.5x52.8

280/617
AFC-11030 30KVA 250.0 125.0 330/727.6
AFC-31010 10KVA 83.3 41.7


120/208V
or   277/480V
or   220/380 V
± 15% (3Ø4W +G)
600x850x945/
23.7x33.5x37.3
240/529
AFC-31015 15KVA 125.0 62.5 600x850x1340
/23.7x33.5x52.8

290/639
AFC-31030 30KVA 250.0 125.0 360/793
AFC-31045 45KVA 375.0 187.5 800x860x1545/
31.5x33.9x60.9

580/1278
AFC-31060 60KVA 500.0 250.0 670/1477
AFC-31080 80KVA 666.7 333.4 1050x970x1800/ 830/1829
41.4x38.2x70.9
AFC-31100 100 KVA 833.3 416.7
£3%*

³85%
1150x1240x1900
/45.3x48.9x74.9

935/2061
AFC-31120 120 KVA 1000.0 500.0 1092/2407

 

 1. AFC series have input overvoltage, undervoltage, overcurrent, over power, output overvoltage, undervoltage, reverse current, over temperature and short circuit protection
* The test situation is under resistive load. ** All specifications are subject to change without notice.
***All dimensions and weights are for input voltage 220/380V. Please contact us for dimensions for other input voltage.



AFC Series-Three Phase Unit

Three-phase output models

Model
Output Input Dimensions (WxDxH)
mm / inch

Chassis No.

Weight KG / lbs

Power

Phase
Voltage (Vrms)
Frequency
Current / Phase
THD

Regulation
Frequency Accuracy
Efficiency

Voltage

Frequency
Power Factor
Low
(Arms)
High
(Arms)
AFC-33005 5KVA







3Ø4W
+G





Low(V): 5-150 VAC
High(V): 10-
300VAC (L-N)
A
(Standard) 47~63Hz,
50/60Hz
B    45~500Hz

C      350~450Hz,
400Hz
D    47~63Hz,
50/60/2F/
4F/400Hz
E    50/60Hz
13.9 6.9




£2% * (opt.
£1%,
up to 200kVA)







± 1% *







£0.01%



³90%





120/208V
or   277/480V
or   220/380V
± 15% (3Ø4W +G)







50 or 60 ±3
Hz







³0.8
600x850x945 200/441
/23.7x33.5x37.3
AFC-33010 10KVA 27.8 13.9 600x850x1340
/23.7x33.5x52.8
300/661
AFC-33015 15KVA 41.7 20.8 310/683
AFC-33030 30KVA 83.3 41.7 410/903
AFC-33045 45KVA 125.0 62.5 800x860x1545 580/1278
AFC-33060 60KVA 166.7 83.3 /31.5x33.9x60.9 670/1477
AFC-33080 80KVA 222.2 111.1 1050x970x1800 890/1962
AFC-33100 100KVA 277.8 138.9 /41.4x38.2x70.9 960/2116
AFC-33120 120KVA 333.3 166.7

1170/2579
AFC-33160 160KVA 444.4 222.2 1150x1240x1900 1400/3086
AFC-33200 200KVA 555.6 277.8 /45.3x48.9x74.9 1840/4056
AFC-33240 240KVA 666.7 333.3 ³85% 2220/4894
AFC-33300 300KVA 833.3 416.7 2240x1240x2000 2465/5434
AFC-33400 400KVA 1111.1 555.6 /88.2x48.9x78.8 3335/7352
AFC-33500 500KVA 1388.9 694.4 3450x1240x2000 3600/7936
AFC-33640 640KVA 1777.8 888.9 /135.8x48.9x78.8 3960/8730

AFC series have input overvoltage, undervoltage, overcurrent, over power, output overvoltage, undervoltage, reverse current, over temperature and short circuit protection

* The test situation is under resistive load. ** All specifications are subject to change without notice.
***All dimensions and weights are for input voltage 220/380V. Please contact us for dimensions for other input voltage.